Before You Add Start Assist, Find Out Why the Compressor Is Struggling
Before you add start assist, find out why the compressor is struggling.
An outdoor AC unit that hums, clicks, dims the lights, or trips a breaker may be having trouble starting. Those symptoms do not identify the cause, however, and they do not prove that an AC hard-start kit is the correct repair.
A hard-start kit can provide brief starting assistance to certain compatible single-phase compressors. It cannot replace a failed run capacitor, repair burned contacts, correct poor supply voltage, clear an airflow or refrigerant problem, or restore a mechanically damaged compressor.
The sound approach is measurement-first: identify the equipment, investigate the electrical and operating conditions, repair actual faults, check manufacturer documentation, and then decide among component repair, start assistance, soft starting, compressor work, or equipment replacement.
This is a consumer decision guide, not a wiring or service procedure. The available evidence comes mainly from HVAC contractors, retailers, a manufacturer, and technical-forum contributors rather than independent controlled studies or model-specific compressor service literature. A qualified HVAC professional should adapt any diagnostic discussion to the exact equipment and its manufacturer’s instructions.
What “AC Hard Start” Means—and What a Hard-Start Kit Actually Does
“Hard starting” describes a condition, not a particular accessory. It means a compressor or motor struggles to engage, accelerate to operating speed, or remain running during startup. The compressor may hesitate, hum without moving, make repeated attempts, or start and then stop.
A hard-start kit, by contrast, is a start-assist device. In a conventional application, it is used with a compatible single-phase air-conditioning or heat-pump compressor. The usual arrangement combines:
- A start capacitor that provides additional electrical starting assistance
- A relay or another switching method that removes that capacitor from the circuit after the compressor starts
This assistance is momentary. Once the compressor reaches operating speed, it continues through its normal running circuit; the start capacitor is no longer supposed to participate. A hard-start kit therefore affects startup rather than ordinary cooling operation.
The added capacitance is intended to increase available starting torque. More torque can help a compatible compressor accelerate faster and spend less time stalled or near stalled.
That does not mean every kit reduces peak current. Several related measurements are often blurred together:
- Available starting torque
- Instantaneous or peak starting current
- Startup duration
- Supply-voltage sag
- Energy consumed over the complete starting event
A compressor may draw a higher instantaneous current yet reach operating speed sooner. It may also spend less time drawing elevated current without producing a lower measured peak. Voltage-sag results depend on the compressor, start-assist device, electrical source, conductors, controls, and switching behavior.
The central distinction is simple: an AC hard-start kit is an accessory for a confirmed starting problem on compatible equipment. It is not a universal compressor upgrade, and installing one is not a diagnosis.
Warning Signs: Symptoms That Merit Diagnosis, Not an Automatic Kit
None of the following observations uniquely diagnoses a need for start assistance. The same symptom can arise from the compressor, capacitor, contactor, wiring, supply circuit, controls, airflow, or refrigeration system.
| What you observe | Possible cause categories | Appropriate response |
|---|---|---|
| Compressor hums but does not start | Weak or failed capacitor, low supply voltage, loose connection, damaged contactor, incorrect control signal, internal compressor resistance or damage | Stop repeated attempts and have the starting circuit, supply, and compressor evaluated |
| Clicking or repeated attempts | Contactor or control operation, overload response, low voltage, loose wiring, capacitor trouble, compressor stalling | Identify what is switching and why rather than assuming the compressor only needs more torque |
| Delayed startup | Weak capacitor, voltage sag, poor connection, difficult mechanical startup, unfavorable refrigeration conditions | Measure voltage and current during the delay and inspect existing components |
| Starts and immediately shuts down | Overload response, electrical or control fault, compressor problem, refrigeration pressure issue, inadequate airflow | Determine which control or protective event is ending operation |
| Short cycling | Thermostat or control problem, airflow restriction, refrigeration fault, electrical interruption, compressor overheating or overload operation | Diagnose cycle termination separately from the initial start |
| Lights dim noticeably | Voltage sag, defective or inadequate supply path, loose connection, demanding compressor start, limited generator or inverter capacity | Investigate voltage behavior; dimming alone does not identify the remedy |
| Breaker trips during startup | Circuit or compressor fault, excessive current, damaged wiring, incorrect protection, failed component | Stop repeated resets and arrange diagnosis of the circuit and compressor |
Repeated breaker resets should not be used to force another start, and protective devices should never be bypassed merely to keep the compressor running. Breaker trips, dimming, humming, and short cycling can reflect underlying electrical or mechanical faults rather than a proper start-assist application, as this retailer’s warning-sign discussion also cautions.
Weak capacitors, loose wiring, and internal mechanical resistance are among the possible causes identified in a service provider’s discussion of common AC hard-start causes. Such lists are useful for defining what needs investigation, but they cannot establish which component has failed.
Humming or delayed starting
Possible causes include:
- A weak or failed run capacitor
- Low voltage at the equipment
- Excessive voltage drop through the supply path
- Loose, burned, or defective connections
- A contactor that is not conducting reliably
- Internal winding or mechanical trouble
A start-assist kit installed over a failed run capacitor does not repair that capacitor. Nor does it correct overheated terminals, defective contacts, or an inadequate electrical supply.
Repeated unsuccessful attempts can also expose the system to additional protective trips and heating. The appropriate response is to stop forcing restarts and determine why the compressor is not accelerating.
Clicking and repeated attempts
A click may be the contactor operating, a control switching, or an overload interrupting an unsuccessful start.
The technician needs to identify what is clicking and what condition is causing it. Treating every repeated attempt as a shortage of starting torque risks overlooking the component that is actually interrupting power.
Immediate shutdown and short cycling
A compressor that starts and stops almost immediately may have a startup problem, but “short cycling” encompasses more than startup.
The useful question is not simply whether the cycle was short. It is what command, fault, or protective event stopped the system.
Light dimming and breaker trips
Brief light movement can accompany supply-voltage sag when a large motor starts. Severe, newly developed, or prolonged dimming deserves investigation, but it does not establish whether the remedy is start assistance, a supply repair, or something else.
A breaker trip is more urgent. Do not normalize the trip, increase breaker capacity without an appropriate engineering basis, bypass protection, or keep resetting the breaker. Diagnosis should cover both the supply circuit and the compressor.
The Diagnostic Sequence Before Start Assist Is Considered
The following sequence is a discussion checklist rather than a universal service protocol. A qualified technician may change the order for safety, model-specific procedures, or the fault observed.
-
Identify the outdoor unit and compressor completely. Record the outdoor-unit and compressor model information. Determine the supply voltage and phase; whether the equipment is single-stage, two-stage, variable-capacity, or inverter-driven; whether factory start components are already present; and whether the equipment remains under warranty.
-
Inspect the power path. Examine the relevant supply circuit, disconnect, conductors, terminals, contactor, and connections for looseness, overheating, discoloration, corrosion, or damage. A start-assist device should not be used to push through a defective connection or inadequate supply path.
-
Assess existing capacitors and factory start components. Evaluate the run capacitor and any factory-installed start capacitor, relay, or electronic starting control. A failed existing component calls for repair or replacement under the applicable equipment documentation—not an additional accessory intended to conceal the failure.
-
Measure supply voltage during an attempted start. Static voltage while the system is idle does not reveal the complete starting condition. A technician may need to observe voltage during the attempted start and determine where meaningful voltage drop occurs.
-
Assess startup current behavior. Startup amperage or an available current trace can be compared with relevant compressor nameplate and manufacturer information. Locked-rotor amperage may inform the evaluation where applicable, but it is not a universal threshold that automatically authorizes a hard-start kit.
-
Observe compressor behavior. Questions may include whether the compressor starts on the first command, how long acceleration takes, whether it remains stalled, whether it drops out on protection, and whether it retries. Evidence suggesting winding or internal mechanical damage points toward a different repair decision.
-
Investigate controls, airflow, and refrigeration conditions. If the compressor starts but operation ends rapidly—or if airflow, temperatures, pressures, or control signals are abnormal—those systems require their own diagnosis. Startup and operating faults can overlap without sharing the same cause.
-
Consult the manufacturer’s documentation. Determine whether the equipment requires, permits, already includes, or prohibits start assistance. If an accessory is approved, selection should follow the specified part number or matching criteria rather than nominal tonnage alone.
If an approved device is installed, useful before-and-after observations may include:
- Startup voltage
- Current behavior
- Start duration
- Whether the compressor starts on the first command
- Whether the start capacitor leaves the circuit as intended
- Whether source-voltage sag or light dimming changes
These are examples of verification questions, not a universal test specification. There is no supported voltage-sag percentage, amperage value, or start-time threshold that determines whether every residential AC needs a kit.
Improvement should be measured where practical, not inferred solely because the compressor sounds different or the lights appear steadier.
Decision Guide: When a Hard-Start Kit May Help—and When It Will Not
Begin with one question:
Does the compressor start normally?
If yes: do not assume it needs an aftermarket kit
If the compressor engages promptly, accelerates normally, stays running, and produces no abnormal electrical observations, there is little demonstrated reason to add routine aftermarket start assistance.
“Single-stage” describes how equipment operates; it is not a diagnosis. Manufacturer documentation may call for a start accessory under a defined installation condition, but that is different from adding a generic kit preventively to every normally operating compressor.
If no: diagnose and correct faults first
When startup is difficult, the investigation should address possible defects involving:
- The run capacitor or factory start components
- Contactor contacts or coil operation
- Wiring, terminals, or the disconnect
- Supply voltage and the branch circuit
- Thermostat or control signals
- Refrigeration conditions
- Indoor or outdoor airflow
- Compressor windings or mechanical condition
Start assist cannot repair a weak capacitor, burned contactor, loose conductor, poor supply, airflow restriction, refrigerant fault, or damaged compressor. Installing an accessory without addressing the actual failure may temporarily change the symptom while leaving the fault in place.
If no external fault remains: evaluate candidacy
A defensible candidate has all three of these characteristics:
- Difficult starting is measured or repeatedly confirmed.
- No unresolved external electrical, control, airflow, or refrigeration fault explains it.
- The manufacturer permits the specific start-assist device being considered.
Commercial field guidance sometimes identifies marginal voltage, long or elevated refrigerant line sets, frequent restarting, an aging compressor, or another difficult-start condition as a reason to investigate. These are not automatic installation rules. Each circumstance must be connected to actual startup behavior and evaluated under the manufacturer’s instructions.
Choose the outcome that matches the cause
The diagnosis should lead to one of five branches:
-
Repair a defective component. Repair or replace a failed capacitor, contactor, terminal, conductor, control, or other identified component.
-
Correct the power, airflow, or refrigeration problem. Resolve excessive voltage drop, an inadequate supply path, airflow restrictions, abnormal control behavior, or a refrigerant-system fault.
-
Install OEM-approved start assistance. Use a correctly matched device when difficult starting is confirmed and the equipment manufacturer permits it.
-
Evaluate a soft starter. Consider electronic current management when the principal objective is managing source demand rather than adding starting torque.
-
Assess compressor or system replacement. Move toward replacement analysis when internal mechanical or winding damage is confirmed, the compressor still cannot start reliably after correctable faults are addressed, or the broader equipment condition makes another accessory-based intervention imprudent.
A kit may sometimes help a compatible, marginal compressor complete startup. In that situation, it is more prudent to discuss the accessory as a possible temporary aid accompanied by replacement planning—not as a guaranteed extension of compressor life. Commercial guidance likewise describes start assist as a temporary measure rather than an underlying repair.
Compatibility and Selection: Why Tonnage Alone Is Not Enough
The first compatibility question is not “How many tons is the AC?” It is “What does the manufacturer permit for this exact outdoor unit, compressor, and control design?”
| Equipment type | Generic aftermarket hard-start kit? | What decides the issue |
|---|---|---|
| Conventional single-stage, single-phase compressor | May be a candidate after diagnosis | OEM approval, confirmed starting behavior, compressor specifications, existing components |
| Single-phase heat pump | Possibly, but not automatically | Heat-pump controls, operating modes, factory components, and manufacturer documentation |
| Two-stage system | Do not make a categorical assumption | OEM control design and instructions for the specific model |
| Variable-speed system | Presume unsuitable without explicit approval | Manufacturer-approved accessory and integration instructions |
| Inverter-driven compressor | Do not add a generic kit | The inverter and compressor operate as an engineered electronic system |
| Equipment with factory start assist | Usually unnecessary unless OEM instructions say otherwise | Condition of factory components and applicable service documentation |
| Equipment with factory soft start or engineered electronic controls | A generic addition may conflict with control operation | Explicit authorization for a specific accessory and procedure |
A conventional single-stage compressor may be eligible for start assistance, but its stage designation alone is insufficient. Heat pumps also require model-specific evaluation because controls and operating conditions may differ from those of cooling-only equipment.
Two-stage systems should not be approved or rejected solely by category. The control design and manufacturer’s documentation should decide the issue.
Variable-speed and inverter-driven equipment warrant a stronger presumption against generic modifications. Their compressors are managed by purpose-designed electronics. A conventional capacitor-and-relay accessory should not be attached unless the manufacturer explicitly identifies and approves the device and procedure.
A technician should verify, as applicable:
- OEM accessory or part-number guidance
- Outdoor-unit model
- Compressor model
- Voltage
- Phase
- Locked-rotor amperage
- Nominal capacity
- Existing run and start components
- Contactor and control arrangement
- Relay or switching design
- Warranty status
Retail listings demonstrate product diversity, not compatibility with a particular AC. Devices sold in the same category vary by capacity range, voltage, capacitance, horsepower, and whether they use a potential relay, PTC device, or another switching arrangement, as illustrated by this hard-start and soft-start product listing.
Overlapping advertised tonnage or horsepower ranges do not make two products interchangeable. The compressor’s electrical characteristics and the method and timing used to remove the start capacitor also matter.
Before purchase, ask the installer to identify the applicable manufacturer document or accessory reference. A package label containing the unit’s nominal tonnage is not, by itself, evidence of compatibility.
Hard Start vs. Soft Start: Added Torque and Managed Current Are Different Goals
Despite their similar names, a hard-start kit and an electronic soft starter do not address startup in the same way.
| Comparison point | Hard-start kit | Electronic soft starter |
|---|---|---|
| Primary objective | Provide brief starting assistance and additional torque | Manage or ramp startup current more gradually |
| General approach | Adds a start capacitor and removes it through a switching device | Electronically controls the startup process |
| Startup-current behavior | System-dependent; added capacitance does not guarantee a lower peak | Intended to limit or manage starting demand |
| Startup duration | Generally intended to accelerate the compressor more quickly | May use a more controlled acceleration interval |
| Typical decision context | Confirmed difficult start requiring additional torque | Current management, limited-source operation, or voltage-sag concerns |
| Control complexity | Usually a simpler capacitor-and-switching arrangement | More complex electronic control |
| Compatibility | Requires compressor and OEM matching | Requires compressor, source, control, and OEM matching |
“Hard start” does not mean “high-current reduction.” A conventional kit provides a firm, brief assist intended to increase torque and get the compressor moving before the added capacitor is removed.
A soft starter instead manages how current is applied during acceleration. Its objective is generally a controlled demand profile rather than a conventional momentary torque boost. The two technologies should not be treated as interchangeable.
Generator and inverter applications
Starting a compressor can be difficult for a generator or inverter with limited capacity. Cable-related voltage drop may compound the problem. That does not establish that either a hard-start kit or a soft starter is universally correct.
Eltwin, a soft-starter manufacturer, argues that current-managed starting is better suited to generator- and inverter-powered HVAC applications. That is the manufacturer’s product-positioning claim, not independent proof for every compressor and power source; its reasoning appears in Eltwin’s hard-start and soft-start comparison.
For backup-power or off-grid operation, compare:
- Measured compressor starting demand
- Voltage behavior at the equipment
- Available generator or inverter capacity
- Cable-related voltage drop
- Compressor and control compatibility
- Manufacturer approval
- The actual objective: additional starting torque or managed source demand
A universal generator-sizing formula would be misleading here.
What the Evidence Supports—and What Hard-Start Marketing Overstates
Claims about AC hard-start kits range from straightforward descriptions of circuit function to broad promises about energy bills and compressor life. They do not deserve equal confidence.
| Claim | What can be said | Evidence limitation | What should be measured |
|---|---|---|---|
| “It adds starting assistance.” | Supported as the basic intended function of a conventional capacitor-and-switching-device kit | Actual performance depends on the compressor and switching design | Start duration, voltage, current profile, successful first-attempt starts |
| “It always reduces inrush current.” | Not established as a universal result | Sellers and technical contributors disagree; peak current and duration are often conflated | Peak current, current over time, voltage sag, start duration |
| “It lowers electric bills.” | Meaningful routine residential savings are not established by the available evidence | Startup occupies only a small part of ordinary operation, and no independent savings data are supplied | Whole-system energy use over a representative period |
| “It improves efficiency.” | It does not change the unit’s certified SEER or SEER2 rating | Startup assistance does not alter the certified rating for normal operation | Do not infer efficiency from a faster-sounding start |
| “It extends compressor life.” | Reducing a confirmed starting difficulty is a plausible intended benefit | No independent long-term data establish a predictable lifespan increase | Long-term failure and field data, not one startup observation |
| “Every single-stage system needs one.” | Not supported as a general rule | This is a contractor opinion contradicted by more cautious guidance | Evidence of an actual starting problem and OEM requirements |
Starting assistance is the best-supported claim
The core function is relatively straightforward: a start capacitor provides temporary assistance, and a relay or other switching device removes it after startup. That description does not prove a particular compressor needs the accessory; it only explains what a conventional kit is intended to do.
“Lower inrush” requires precise definitions
Retail listings advertise inrush reductions, torque increases, shorter starts, and equipment-protection benefits. Those figures are marketing claims without disclosed universal test conditions, even though the listings usefully demonstrate that ratings and relay designs vary.
Technical discussion offers a different explanation. In a Mike Holt electrical forum, moderator Jraef and other contributors distinguish a hard-start kit’s additional torque from a soft starter’s current-management function. The discussion is not a formal standard or controlled study, but it illustrates why higher instantaneous current can coexist with shorter acceleration.
Both of these results can occur:
- The measured current peak can be higher.
- The elevated-current interval can be shorter.
Peak current, current over time, voltage sag, and total starting energy are therefore not synonyms. Device-specific measurement is more useful than a generic percentage in an advertisement.
Ordinary bill savings are not established
A hard-start device participates only during startup. It does not continuously reduce compressor power while the system cools the home. The available evidence does not establish meaningful routine residential electricity savings; contributors in the same electrical discussion note that startup energy is a small part of ordinary consumption, while also distinguishing that issue from separately billed peak demand.
Startup performance can still matter to a facility billed for peak demand or to a property operating from a limited generator or inverter. That is a different financial question from promising an ordinary homeowner a material monthly bill reduction.
SEER and SEER2 do not change
SEER and SEER2 are certified equipment ratings. Adding a momentary start-assist accessory does not rewrite those ratings or establish a more efficient normal cooling cycle, according to the available commercial HVAC compatibility and efficiency guidance. A faster start should not be advertised as a higher-efficiency cooling system.
Lifespan claims are plausible in theory but unproven in duration
Helping a suitable compressor avoid repeated failed starts may be a reasonable intended benefit. The supplied evidence does not establish that a kit will extend compressor life by a predictable number of months or years.
One contractor recommends start kits broadly for new single-stage equipment and claims substantial reductions in startup strain, but its hard-start explanation does not provide independent testing sufficient to turn that recommendation into a general rule.
The evidence base overall remains limited. Contractors and retailers can provide useful field observations; product listings can show design differences; a manufacturer can explain its own technology; and forum contributors can identify disputed technical interpretations. None of those sources replaces model-specific OEM documentation, independent testing, or qualified review of the actual system.
The practical response is to reject generic percentage, savings, and lifespan promises and request before-and-after measurements for the proposed device, compressor, and supply.
Safety, Warranty, and the Final Repair-or-Replace Decision
Air-conditioning service involves hazardous voltage, and capacitors can retain electrical charge after power is disconnected. Incorrect selection, unsafe capacitor handling, or miswiring can create risks of electric shock, fire, control conflict, and compressor damage. Qualified diagnosis and installation are prudent, and manufacturer approval matters because a nonapproved accessory may conflict with controls or affect warranty coverage under the applicable terms, as cautioned in this HVAC safety and compatibility guide.
This is not an appropriate place for step-by-step capacitor discharge, live testing, wiring, or installation instructions. Professional service is particularly important for:
- Newer or warrantied equipment
- Heat pumps
- Two-stage systems
- Variable-speed systems
- Inverter-driven compressors
- Equipment with electronic or communicating controls
- Systems already fitted with factory start or soft-start components
Before allowing an aftermarket modification, ask for the relevant OEM accessory documentation and review the warranty terms. Electrical fit alone does not establish manufacturer authorization.
Final decision checklist
Before approving a hard-start kit, confirm:
- Cause: Has the reason for difficult starting been identified?
- External faults: Have defective capacitors, contacts, wiring, controls, airflow, refrigeration conditions, and supply problems been addressed?
- Measured need: Do voltage, current behavior, start duration, or repeated observations confirm a startup problem?
- OEM approval: Does the manufacturer permit the proposed accessory?
- Correct match: Was it selected using the compressor model, voltage, phase, electrical data, controls, and switching design—not tonnage alone?
- Compressor condition: Is there evidence of internal mechanical or winding damage?
- Equipment condition: Does the rest of the system justify further repair?
- Warranty: Has the effect of the modification on existing coverage been checked?
- Verification: Will the installer record appropriate before-and-after startup observations?
The repair branch
Choose repair when testing identifies a failed run capacitor, contactor, wiring connection, supply component, airflow restriction, refrigerant fault, or control problem. Correcting the failed item addresses the cause; adding start assistance does not.
The start-assist branch
Choose start assistance when difficult starting is confirmed, the compressor is otherwise a suitable candidate, correctable faults have been resolved, and the manufacturer permits the correctly matched accessory. Verify the result with measurements rather than sound alone.
The replacement branch
Consider compressor or system replacement when internal damage is confirmed, the compressor cannot start reliably after repairable faults have been corrected, or the broader equipment condition makes another accessory-based intervention imprudent.
Compressor condition, warranty, parts availability, refrigerant considerations, repair scope, expected reliability, and the state of the remaining equipment all matter.
Frequently Asked Questions
Does every single-stage air conditioner need a hard-start kit?
No. Single-stage operation can make a conventional compressor a possible candidate for start assistance, but it does not prove that assistance is needed.
If the compressor starts promptly and reliably, there is little demonstrated benefit from adding a routine aftermarket kit. Installation is more defensible when difficult starting is confirmed, other faults have been addressed, and the manufacturer approves the selected accessory.
Can a hard-start kit stop my breaker from tripping or my lights from dimming?
It may change startup behavior in a compatible, correctly diagnosed application, but neither symptom guarantees that it will.
Dimming can reflect voltage sag, wiring trouble, loose connections, or a limited power source. A breaker may trip because of circuit defects, excessive current, damaged wiring, a failed component, or compressor trouble. Stop repeated resets and have the circuit and compressor diagnosed rather than using start assist to conceal protective-device operation.
Does a hard-start kit improve SEER2 or reduce my electricity bill?
It does not change the equipment’s certified SEER or SEER2 rating. The device acts during startup, not throughout the normal cooling cycle.
The available evidence also does not establish meaningful routine residential electricity savings. Startup behavior can matter for voltage sag, peak demand, generators, or inverters, but that is different from improving certified efficiency or materially reducing ordinary energy consumption.
Can a hard-start kit be installed on a variable-speed or inverter AC?
A generic aftermarket kit should not be added without explicit manufacturer approval. Variable-speed and inverter systems use engineered electronics to manage compressor operation, and a conventional capacitor-and-relay accessory may conflict with those controls.
Consult the exact unit’s service documentation. If the manufacturer identifies a designated accessory and procedure, follow that guidance; otherwise, do not infer compatibility from tonnage or supply voltage.
Is a hard-start kit a permanent repair for a failing compressor?
No. It may help a compatible, marginal compressor complete startup, but it cannot repair internal mechanical damage, damaged windings, or a failed compressor.
When used on an aging or marginal compressor, start assist should be discussed as a possible temporary aid alongside replacement planning. If the compressor still cannot start reliably after external faults have been corrected, another accessory is unlikely to substitute for compressor or equipment replacement.
The Measurement-First Rule
A useful script for the service visit is:
What failed, and what measurements confirm it? What readings show that this compressor is hard starting? Does the manufacturer approve this device for the exact unit and compressor? How was the kit matched? What voltage, current, and start-time observations will be recorded afterward to verify the result?
Do not buy start assistance merely because the AC hums, dims the lights, or trips a breaker. Identify the equipment, investigate the supply and starting circuit, repair actual faults, confirm OEM approval, and install a correctly matched device only when difficult starting is verified.
A hard-start kit can be useful in a narrow, compatible case. It is neither preventive medicine for every compressor nor a substitute for repairing or replacing damaged equipment.